How the wire size is picked
Two checks, and the bigger answer wins:
- Ampacity. The wire must carry the current without overheating. We use NEC Table 310.16: NM-B (Romex) and UF cable use the 60 °C column; THHN/THWN in conduit uses 75 °C, the usual rating of breaker and device terminals. Loads that run 3 hours or more (EV chargers, water heaters, space heaters) are sized at 125%. Small wires also have breaker limits: 14 AWG copper on 15 A, 12 AWG on 20 A, 10 AWG on 30 A.
- Voltage drop. Long runs lose voltage in the wire itself. The NEC recommends no more than 3% on a branch circuit (5% including the feeder), so motors start and lights don't dim. Drop = 2 × length × resistance × amps ÷ 1,000 for single-phase (√3 instead of 2 for three-phase).
| Copper wire | NM-B (60 °C) | THHN (75 °C) | Typical use |
|---|---|---|---|
| 14 AWG | 15 A | 15 A | Lighting circuits |
| 12 AWG | 20 A | 20 A | Kitchen and bath outlets |
| 10 AWG | 30 A | 30 A | Dryer, water heater |
| 8 AWG | 40 A | 50 A | Range, 40 A EV charger |
| 6 AWG | 55 A | 65 A | 50 A EV charger, subpanel |
| 4 AWG | 70 A | 85 A | Subpanel |
| 2 AWG | 95 A | 115 A | 100 A subpanel (75 °C) |
For planning only. Local codes, conduit fill, ambient temperature and the equipment's own instructions can call for a bigger wire. Electrical work usually needs a permit.
The two checks
The wire size calculator picks the smallest wire that passes two tests. Ampacity means the wire carries the current without overheating, using NEC Table 310.16. Voltage drop means a long run does not lose too much voltage, with 3% recommended on a branch circuit. The larger answer wins.
NM-B (Romex) and UF cable use the 60 °C column, and THHN or THWN in conduit uses 75 °C, the usual rating of breaker and device terminals. Loads that run for three hours or more, such as EV chargers, water heaters and space heaters, are sized at 125%.
Copper wire ampacity
The table shows the ampacity of copper at the two temperature ratings, and a typical use. Small wires also have breaker limits: 14 AWG copper on 15 amps, 12 AWG on 20 and 10 AWG on 30. These are for planning, so check the code in your area.
| Wire | NM-B (60 °C) | THHN (75 °C) | Typical use |
|---|---|---|---|
| 14 AWG | 15 A | 15 A | Lighting circuits |
| 12 AWG | 20 A | 20 A | Kitchen and bath outlets |
| 10 AWG | 30 A | 30 A | Dryer, water heater |
| 8 AWG | 40 A | 50 A | Range, 40 A EV charger |
| 6 AWG | 55 A | 65 A | 50 A EV charger, subpanel |
| 4 AWG | 70 A | 85 A | Subpanel |
| 2 AWG | 95 A | 115 A | 100 A subpanel (75 °C) |
Conduit fill, ambient temperature and the equipment's own instructions can call for a bigger wire than the table shows.
How far can each wire go?
This table gives the one-way length at which voltage drop reaches 3% on 240 volts, for copper wire at the current shown. Ampacity can rule out a smaller wire before distance does, so check both. A 10 AWG wire, for instance, cannot carry a 40 or 50 amp load whatever the distance.
| Load | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|---|---|---|---|
| 30 A at 240 V | 99 ft | 157 ft | 244 ft | 390 ft |
| 40 A at 240 V | 74 ft | 118 ft | 183 ft | 292 ft |
| 50 A at 240 V | 60 ft | 94 ft | 147 ft | 234 ft |
A 30 amp circuit on 10 AWG copper works up to about 95 feet at 240 volts. Longer runs need 8 AWG to keep drop under 3%.
The 125% rule
A continuous load is one that runs for three hours or more. The NEC requires the circuit to be sized at 125% of it. A 40 amp EV charger is therefore sized as 50 amps, which needs a 50 amp breaker and 6 AWG NM-B or 8 AWG THHN at 75 °C. Tick the continuous option in the calculator to apply it.
Water heaters, space heaters and some pumps are treated the same way. If unsure, treat any load that runs for hours as continuous.
NM-B or conduit
NM-B cable is common in dry indoor wiring, and has the lower 60 °C ampacity. THHN or THWN wires in conduit use the 75 °C column, which allows a smaller wire for the same current, and are used outdoors, in garages and for heavy circuits. UF cable is rated for direct burial and wet locations.
Conduit costs more and takes more time, but the wires can be pulled later and replaced. Check which types your local code allows.
Aluminum
Aluminum is lighter and cheaper but has about 60% more resistance than copper, so you go up two sizes. A 100 amp subpanel is commonly 2 AWG copper or 1/0 aluminum at 75 °C. Use connectors rated for aluminum and an antioxidant compound, and never mix them with copper-only terminals.
Many feeders to subpanels use aluminum SER cable because it costs far less on long runs.
Long runs and voltage drop
All wire has resistance, so longer runs lose more voltage. A thicker wire has less resistance and keeps the voltage at the far end closer to what the panel supplies. See the voltage drop calculator for the drop in volts and percent for any wire.
For a detached garage or a well pump 200 feet away, voltage drop will often decide the size, not ampacity.
Permits and safety
Electrical work usually needs a permit and an inspection, and many places require a licensed electrician. Turn off the breaker and test that the circuit is dead before touching wires. Never replace a breaker with a larger one without checking the wire. A breaker protects the wire, not the device.
This calculator is for planning. Local codes, conduit fill, ambient temperature and the manufacturer's instructions can all change the answer. To see what a load costs, use the electricity cost calculator.
Choosing the breaker
The breaker is sized to protect the wire, and must not exceed its ampacity. For a continuous 40 amp load, use a 50 amp breaker. For a motor or a heater, follow the nameplate. Some appliances need a dedicated circuit, which means nothing else shares the wire.
GFCI and AFCI protection are required in many locations, such as kitchens, bathrooms, garages and bedrooms. Check the current code edition used in your area.
More questions people ask
What size wire for 30 amps?
10 AWG copper for a typical 30 A circuit up to about 95 feet at 240 V. Longer runs need 8 AWG to keep voltage drop under 3%.
What size wire for 50 amps?
6 AWG copper NM-B, or 8 AWG copper THHN in conduit with 75 °C terminals. Long runs may need one size bigger.
What size wire for a 100 amp subpanel?
Commonly 2 AWG copper or 1/0 aluminum at 75 °C, more for long runs. The calculator checks voltage drop for your distance.
Why does distance change the wire size?
All wire has resistance, so longer runs lose more voltage. A thicker wire keeps the voltage at the far end closer to what the panel supplies.
Worked examples on this page were calculated with the same formulas as the calculator above. Written and last reviewed by Shaun Longbottom, November 2026.
Frequently asked questions
What size wire for 30 amps?
10 AWG copper for a typical 30 A circuit up to about 95 feet at 240 V. Longer runs need 8 AWG to keep voltage drop under 3%.
What size wire for 50 amps?
6 AWG copper NM-B, or 8 AWG copper THHN in conduit with 75 °C terminals. Long runs may need one size bigger.
What size wire for a 100 amp subpanel?
Commonly 2 AWG copper or 1/0 aluminum at 75 °C (THHN in conduit or SER cable), more for long runs. The calculator checks voltage drop for your distance.
Why does distance change the wire size?
All wire has resistance, so longer runs lose more voltage. A thicker wire has less resistance and keeps the voltage at the far end closer to what the panel supplies.
Was this calculator helpful?