Voltage Drop Calculator

Wire, length and load in: volts lost, percent drop, and the wire that keeps you under your limit.

Voltage Drop Calculator by AIPreciseTools · Open the full calculator ↗

The voltage drop formula

Single-phase and DC: Drop (V) = 2 × L × R × I ÷ 1,000 Three-phase: Drop (V) = 1.732 × L × R × I ÷ 1,000 L = one-way length in feet · R = ohms per 1,000 ft · I = amps

Resistance comes from NEC Chapter 9, Table 8 (uncoated copper and aluminum at 75 °C), for example 1.93 Ω per 1,000 ft for 12 AWG copper. The 2 accounts for current going out and back. This uses resistance only, which is accurate for the wire sizes and power factors in homes; very large conductors on AC with motor loads drop slightly more.

Example: 20 A on 75 ft of 12 AWG copper at 120 V: 2 × 75 × 1.93 × 20 ÷ 1,000 = 5.79 V, or 4.8%. That's over the 3% recommendation. 10 AWG (3.6 V) lands right on the line, and 8 AWG (2.3 V, 1.9%) is comfortably under.

Low-voltage DC (12 V solar, RV, LED strips) is where drop bites hardest: the same 5.8 V would be almost half of a 12 V supply. Keep DC runs short and thick.

Need the whole answer, ampacity included? Use the wire size calculator.

The formula

For single-phase and DC circuits, the drop in volts is two times the one-way length times the wire resistance per 1,000 feet times the current, divided by 1,000. The two accounts for current going out and coming back. For three-phase it is 1.732 instead of 2. Resistance comes from NEC Chapter 9, Table 8, which lists uncoated copper and aluminum at 75 °C.

For 20 amps on 75 feet of 12 AWG copper at 120 volts, the drop is 2 × 75 × 1.93 × 20 ÷ 1,000 = 5.79 volts, or 4.8%. That is over the 3% recommendation. 10 AWG gives 3.6 volts, right on the line, and 8 AWG gives 2.3 volts, or 1.9%.

Drop for 20 amps at 120 volts

The table shows the drop as a percentage of 120 volts for 20 amps of copper wire at four one-way lengths. Anything above 3% is flagged in the calculator. Every three gauge sizes up roughly halves the resistance.

WireOhms per 1,000 ft25 ft50 ft75 ft100 ft
14 AWG3.072.6%5.1%7.7%10.2%
12 AWG1.931.6%3.2%4.8%6.4%
10 AWG1.211.0%2.0%3.0%4.0%
8 AWG0.7640.6%1.3%1.9%2.5%
6 AWG0.4910.4%0.8%1.2%1.6%
4 AWG0.3080.3%0.5%0.8%1.0%
2 AWG0.1940.2%0.3%0.5%0.6%

These figures are for a constant 20 amp load. A circuit carrying less current drops proportionally less.

Copper and aluminum

Aluminum has about 60% more resistance than copper of the same gauge, so you typically go up two sizes to match copper. The table compares resistance per 1,000 feet from the NEC table. Aluminum is lighter and cheaper, and common for large feeders, but it needs connectors rated for it.

GaugeCopper (Ω/1,000 ft)Aluminum (Ω/1,000 ft)Ratio
12 AWG1.933.181.65×
10 AWG1.2121.65×
8 AWG0.7641.261.65×
6 AWG0.4910.8081.65×

Never connect aluminum wire to a device marked for copper only.

How much drop is acceptable

The NEC recommends no more than 3% on a branch circuit and 5% total from the service to the farthest outlet. This is a recommendation, not a requirement, except for some equipment like fire pumps. Motors can overheat, lights dim and electronics misbehave when the supply sags.

Equipment manufacturers may set tighter limits, so check the installation instructions for compressors, pumps and chargers.

How far can I run it?

To find the maximum length, rearrange the formula. At 120 volts and 3%, the allowed drop is 3.6 volts. For 12 AWG at 20 amps, that is 3.6 ÷ (2 × 1.93 × 20 ÷ 1,000) = 46.6 feet. At 240 volts the allowed drop is 7.2 volts, so the run doubles to about 93 feet.

For long runs, higher voltage helps because the same power needs half the current. That is why well pumps and workshops are often wired at 240 volts.

Maximum one-way length for 3% at 120 volts

The table gives the longest one-way run before the drop passes 3% at 120 volts, for copper wire. Halve the current and the length doubles. The numbers are for resistance only.

Current12 AWG10 AWG8 AWG6 AWG
10 A93 ft149 ft236 ft367 ft
15 A62 ft99 ft157 ft244 ft
20 A47 ft74 ft118 ft183 ft
30 A31 ft50 ft79 ft122 ft

Round down, since the real resistance rises with temperature and with poor connections.

Low-voltage and DC circuits

Low-voltage DC is where voltage drop hurts most. The same 5.8 volts lost on a 120 volt circuit is under 5%, but on a 12 volt solar, RV or LED strip circuit it is almost half the supply. Keep DC runs short and thick, and size by drop first and ampacity second.

For solar charge controllers and battery banks, even 2% drop wastes meaningful power over a year.

Where to go next

Voltage drop is one of two checks. The wire must also be thick enough to carry the current safely. The wire size calculator checks both. To work out power, current and resistance together, try the Ohm's law calculator, and to see what a load costs, the electricity cost calculator.

Electrical work usually needs a permit and an inspection. This guide is for planning, so check with a licensed electrician.

Temperature and connections

Resistance rises with wire temperature, and the table values are for 75 °C. A cooler wire has slightly less resistance. Loose or corroded terminals add resistance that the formula does not include, so tighten connections to the specified torque and use the right connectors.

If a long circuit still dims lights, measure the voltage at the load while it runs. A clamp meter and a multimeter show where the drop happens.

More questions people ask

What is an acceptable voltage drop?

The NEC recommends no more than 3% on a branch circuit and 5% total from the service to the farthest outlet. It is a recommendation, not a requirement, except for some equipment like fire pumps.

How far can I run 12 gauge wire at 20 amps?

About 46 feet at 120 V before the drop passes 3%, or about 93 feet at 240 V.

Does aluminum wire have more voltage drop?

Yes. Aluminum has about 60% more resistance than copper of the same gauge, so you typically go up two sizes to match copper.

Why is the length counted once but the formula uses 2?

The length is one way, and the current travels out and back, so the formula doubles it for single-phase and DC circuits.

Worked examples on this page were calculated with the same formulas as the calculator above. Written and last reviewed by Shaun Longbottom, November 2026.

Frequently asked questions

What is an acceptable voltage drop?

The NEC recommends no more than 3% on a branch circuit and 5% total from the service to the farthest outlet. It's a recommendation, not a requirement, except for some equipment like fire pumps.

How far can I run 12 gauge wire at 20 amps?

About 46 feet at 120 V before the drop passes 3%, or about 93 feet at 240 V.

Does aluminum wire have more voltage drop?

Yes, aluminum has about 60% more resistance than copper of the same gauge, so you typically go up two sizes to match copper.

Was this calculator helpful?